Skip to main content
£0.00 0

Basket

No products in the basket.

MINING BUNDLE

12x Antminer S21 Hydro 319TH + 3x Bitmain ANTRACK AR21 Racks

SHA-256 · 3.83 PH/s

12 miners · Hydro cooling · Without container

Back Order
ANTRACK AR21 — unit 1 of 3ANTRACK AR21 — unit 2 of 3ANTRACK AR21 — unit 3 of 3
Antminer S21 — 12 included
Hashrate
3.83 PH/s319 TH/s each
Algorithm
SHA-256
Efficiency
16W/TH
Power
61.25kW5.1kW each
Estimated Power
65.15kW3.9kW auxiliaries (estimated)
Earns/kWh
7.67p
Solo · eCashAuto · Annual comparison
Equipment Price
£39,840.00Ex VAT£42,370.00

Total Saving £2,530.00

£43,797.68₿0.70082277 equivalentGross Payback

Component Miner Rankings

Component miner ranking #50
12x Bitmain Antminer S21 Hydro 319Th SHA-256 Bitcoin MinerOverall #50 · Earnings #152 · Efficiency #172 · Value #58 · ROI #77

These are the included individual miners’ existing ranks. Bundle economics use the complete configuration price, delivery, discount and auxiliary power. Mixed fleets show an average component percentage score, with the individual ranks in its breakdown.

Selected Equipment Schedule

12 miners · 65.15kW estimated operating load. Only the following quantities and products are included in this configuration.

EquipmentQuantityRole
Bitmain Antminer S21 Hydro 319Th SHA-256 Bitcoin Miner12Miner
Bitmain ANTRACK AR213Infrastructure
Price Breakdown & Volume Discount
Miner Subtotal
£29,196.00
Infrastructure Subtotal
£9,270.00
Miner Discount
8%
Recorded AER Delivery Allowances
£3,900.00

The volume discount applies once to current published miner prices, including their embedded delivery allowance. Freight enters the complete package total once. Infrastructure is not discounted. Existing AER £10 rounding applies. Unconfirmed amounts are indicative, not an orderable offer.

Power Consumption & Installation Requirements

Miner Load
61.25kW
Estimated Auxiliaries
3.9kW
Estimated Total
65.15kW
Energy per 24 Hours
1,563.552kWh

Calculation uses listed miner power, published pump and fan ratings, plus a 100W controls allowance per rack. The controls figure is an assumption, not a Bitmain specification. Actual consumption varies with temperature and operating settings. Electricity costs and net payback use this estimate and the selected operating time; they exclude unlisted site equipment.

Auxiliary EquipmentQuantityPer UnitTotal
AR21 pump (published rating)30.45kW1.35kW
AR21 external cooler fan (published rating)30.75kW2.25kW
Controls allowance (estimate, not a published rating)30.1kW0.3kW

Each independent AR21 kit serves four standard S21 Hydro miners. No shared cooler or pooled spare capacity is assumed.

Per-rack Miner Design Load
21.44kW
Per-rack Design Total
22.74kW
Planning Reserve
1.2kW
Published Maximum
24kW

The design check adds 5% miner-power tolerance and retains a 5% reserve against the published 24kW rack maximum. This verifies the catalogue configuration within that reference envelope; it is not approval of a customer’s electrical installation or a guarantee of cooling at every ambient temperature.

Electrical Requirements

Each rack serves four S21 Hydro 319TH miners at the standard 5104W setting. AR21 and miners require 380–415V three-phase, 50–60Hz. The rack specification lists 63A input; the later S21 manual lists 12A maximum per miner. An installer must verify delivered branch connectors, protective devices, earthing, circuit ratings and upstream supply before energising. No phase current or usable supply capacity has been invented from the kW total. Design allowance: +5% miner power, 1.3kW estimated auxiliaries and 1.2kW reserve per rack, all checked against a conservative 24kW overall planning ceiling.

Cooling Requirements

One independent pump/cooler circuit per rack; four standard Hydro miners, not U2/U3 chassis. S21 requires 8–10L/min per miner, matching AR21’s published 32–40L/min total; confirm that flow through each branch at commissioning, with pressure no more than 3.5bar. Use manufacturer-approved 10% organic antifreeze with pH 7.8–8.5, within the later S21 manual’s antifreeze pH range. Initial conductivity below 20µS/cm; replace at 100µS/cm. Keep miner inlet coolant within 20–50°C. AR21 publishes −20 to 40°C ambient and a 5m cabinet-to-cooler distance; actual antifreeze freeze protection and heat rejection must suit the site. Place each external cooler outdoors with unobstructed airflow; verify sustained inlet temperature at full load. These limits are conditions, not a guarantee of rated output at every ambient temperature.

Included Equipment & Site Connections

12x Antminer S21 Hydro 319TH miners and 3x Bitmain ANTRACK AR21 OEM kits. Each AR21 kit includes its mining cabinet with 450W-rated circulation pump and a separate external cooler with a 750W-rated fan. Those pump/cooler assemblies are part of the rack line price, not additional equipment charges. Equipment supply only. Coolant fill, cabinet-to-cooler connecting hoses and fittings, any additional miner adapters or replacement leads, upstream distribution, protective devices, site power/network cables, mounting/site works, installation and commissioning are excluded unless separately itemised. Supplied small accessories and connector revisions must be checked against the delivered packing list before installation. Do not assume unlisted items are included. Existing AER delivery allowances are included once; additional site-specific freight is excluded.

Bitmain AR21 specifications · S21 Hydro product manual

Mining Earnings & Block Odds

Scenario, odds & assumptions

Constant-condition scenario, not a forecast. 100% operating time, £0.000/kWh, 2% pool service fee and 0% Solo service fee. Fees are editable assumptions; confirm your chosen provider’s charges. Network transaction rewards are included in the shared source estimate.

Operating power 65.15kW includes 3.9kW auxiliaries. Miner quantities are fixed. Auxiliary inputs must cover the listed cooling equipment.

Estimated power includes published pump/fan ratings and a 100W controls allowance per rack. That allowance is not a measured or manufacturer-rated load. See Power Consumption & Installation Requirements for the complete calculation.

Bitcoin equivalent is a display conversion of the selected mining routes, not a claim that the hardware mines Bitcoin. Recorded Bitcoin price £62,494.65 at 2026-10-21T10:08:09+00:00.

Auto selects the highest expected annual return after the entered fees and operating electricity for each algorithm. Equipment cost is fixed for the selected configuration. A higher expected Solo return does not mean a reliable payout.

eCash Expected Blocks / Year
4,835.167979
At Least One Block
≈100%
No Blocks
<0.0001%
Block Value
£9.06

Block probabilities use this fleet’s actual hashrate over the selected timeframe. Fractional expected blocks are a statistical average, not part of a block paid to you.

Excludes hosting, maintenance, taxes, finance and other operating charges not explicitly entered. Prices, difficulty, rewards and uptime can change. Network inputs: . Calculated .

Annual alternatives after mining fees, before shared electricity costs
Asset / ModeExpected Earnings
SHA-256 · eCash · Solo£43,797.68
SHA-256 · Quai · Solo£41,811.15
SHA-256 · Fractal Bitcoin · Solo£40,535.04
SHA-256 · Bitcoin Cash · Pool£39,759.95
SHA-256 · Bitcoin Cash · Solo£39,571.43
SHA-256 · eCash · Pool£39,340.97
SHA-256 · Bitcoin · Solo£39,190.23
SHA-256 · Fractal Bitcoin · Pool£38,323.46
SHA-256 · Bitcoin · Pool£37,750.57
SHA-256 · Bitcoin · Pool£37,673.62
SHA-256 · Quai · Pool£36,835.67
SHA-256 · DigiByte · Solo£32,537.75
SHA-256 · DigiByte · Pool£28,114.13

Equipment Scope & Site Requirements

12x Antminer S21 Hydro 319TH miners and 3x Bitmain ANTRACK AR21 OEM kits. Each AR21 kit includes its mining cabinet with 450W-rated circulation pump and a separate external cooler with a 750W-rated fan. Those pump/cooler assemblies are part of the rack line price, not additional equipment charges.

Equipment supply only. Coolant fill, cabinet-to-cooler connecting hoses and fittings, any additional miner adapters or replacement leads, upstream distribution, protective devices, site power/network cables, mounting/site works, installation and commissioning are excluded unless separately itemised. Supplied small accessories and connector revisions must be checked against the delivered packing list before installation. Do not assume unlisted items are included. Existing AER delivery allowances are included once; additional site-specific freight is excluded.